Water Quality Monitoring
For conductivity or resistivity monitoring in RO, pure-water, cooling-water, boiler-water, and process-water systems.
JA-AN-EC400 is an online conductivity controller for industrial water monitoring.
We support OEM/ODM projects and product-specific customization. Contact our team to discuss your technical requirements, branding, and available configuration options.
OEM / ODMCustom ConfigurationTechnical Support
JA-AN-EC400 is an online conductivity controller for industrial water monitoring. Suitable for RO, pure-water, cooling-water, boiler-water, and process-water monitoring. Outdoor water-resistant design supports wall, panel, or pipe mounting.
For conductivity or resistivity monitoring in RO, pure-water, cooling-water, boiler-water, and process-water systems.
| Temperature Compensation | automatic compensation (Pt1000/NTC30K); manual compensation or compensation disabled |
|---|---|
| Reference Temperature | Tref 25 °C |
| Display | LCD with adjustable backlight |
| Dimensions | 144 × 144 × 115(H × W × D) |
| Output Signal | 0/4-20mA; RS485 |
| Power Supply | 100V–260VAC, 50/60Hz; 16V–30VDC |
| Ambient Temperature | 0–50 °C |
| Relative Humidity | 5–85% |
| IP Rating | IP65 |
| Conductivity Measurement | range 20.00 μS/200.0 μS/2000 μS/20.00 mS/200.0 mS; five manually or automatically selected ranges; resolution 0.001 μS/cm; accuracy ±1% (±1 digit) |
| Resistivity Measurement | range 0.00–20.00MΩ/cm; resolution 0.01MΩ/cm; accuracy ±1% (±1 digit) |
| Salinity Measurement | range 0.0–70.0 ppt; resolution 0.1 ppt; accuracy ±1% (±1 digit) |
| Temperature Measurement | range -30.0–+130.0 °C; resolution 0.1 °C; accuracy ±0.2% (±1 digit) |
| Temperature Coefficient | linear temperature compensation (0.00%–20.00%) and nonlinear compensation; no compensation |
The Conductivity measurement specifications are: range 20.00 μS/200.0 μS/2000 μS/20.00 mS/200.0 mS; five manually or automatically selected ranges; resolution 0.001 μS/cm; accuracy ±1% (±1 digit).
The Resistivity measurement specifications are: range 0.00–20.00MΩ/cm; resolution 0.01MΩ/cm; accuracy ±1% (±1 digit).
The Salinity measurement specifications are: range 0.0–70.0 ppt; resolution 0.1 ppt; accuracy ±1% (±1 digit).
Applications include Water Quality Monitoring.
Our technical experts are ready to support your application needs. Contact us for product selection, technical questions, or custom requirements.